Protective Units for Generators


Digital Generator Protection Relay (Vector Jump Relay) VECFU5
 
VECFU 5

Acc. to german EVU-standards for protective equipments
Rapid phase jump triggering within 20 – 40ms
High-contrast LCD display
Displays frequency with 2 places after the decimal point
Optimum generator protection for mains failure in parallel operation
Easy-to-use menu control for parameter adjustment and display
Settings can be changed during operation
Threshold values, hysteresis and output changeover contacts for over-
   and underfrequency and for over- and undervoltage



Download specifications (.PDF)
VECFU5 / 3/4-conductor 231V/400V 45 – 70Hz, Cl. 0.5
VECFU5 with R.O.C.O.F.

This unit protects the generator when phase jumps occur in mains-parallel operation and constantly monitors the 3-phase mains voltage applied and the mains frequency in mains-parallel operation. The output contacts for phase jump, undervoltage and underfrequency are switched as working contacts which automatically switch off the system when undervoltage or underfrequency errors occur. As the rapid switch-off provided by the phase monitoring function causes the unit to immediately disconnect from the mains, there is no short-circuit switch-off (with subsequent total failure), so the system can be automatically reconnected to the mains after a certain mains settling time.




Mains / Generator Protecting Relay VECFU1 (discontinued)
 
VECFU 5

Rapid phase jump triggering within 10 - 50ms
Threshold value notification under-/overvoltage of each single phase
   (normally closed contact ) and LED
Threshold value notification of under-/overfrequency with normally closed contact and LED
Optimum generator protection for mains failure in parallel Operation
Easy adjustment of the parameters
Phase jump detection between 1 and 20 degrees
Adjustable mains stabilization time for mains return


Download data sheets (.PDF)
VECFU1 4-conductor N 231V 50Hz +/-20%

This unit protects the generator when there are phase jumps in parallel operation and constantly monitors the 2-phase mains voltage applied and the mains frequency.The output contacts are switched as normally open contacts so that the system swiches off automatically when faults occur. As a result of the rapid switch-off, short circuit switch off ( with subsequent total failure ) does not yet take place, so the system can be automatically connected to the mains again after a mains stabilization time.




Mains / Generator Protection Relay VEC100 (discontinued)
 
VEC100

Rapid phase jump triggering within 10 - 50ms
Optimum generator protection for mains faillure in parallel operatio
Phase jump detection between 1 and 20 degrees
Adjustable mains stabilization time for mains return

Note:
Only 2 conductors ( L-N or L-L ) are required to detect the phase jump as frequency and phase changes occur on all phases with the same magnitude. One-phase monitoring of teh three-phase mains is thus completely sufficient.


Download data sheets (.PDF)
VEC100 2-conductor 231V 50Hz

The unit protects the generator when there are phase jumps in parallel mains operation. The output pads are switched as normally open contacts so that the system switches off automatically, even at mains faillure. When the preset phase jump value is exceeded, the output contact opens within 10 - 50ms. As a result of the rapid switch-off, short circuit switch off ( with subsequent total faillure ) does not yet take place, so the system can be automatically connected to the mains again after a mains stabilization time.




Reverse Power Time Relay RLZ110, RLZ113, RLZ150, RLZ153
 
RLZ 150

Real reverse power measurement throught four-quadrant detection
Precise triggering even in extreme phase position cos-phi
Setting range 2 - 20% reverse power
Delay of triggering 1 - 40sec
Output with two-way contact
LED displays for exceeding and triggering


Download data sheets (.PDF)
RLZ110 4-conductor symm. 231V, 1A (IR)
RLZ150 4-conductor symm. 231V, 5A (IR)
RLZ113 3-conductor symm. 231V, 1A (IR)
RLZ153 3-conductor symm. 231V, 5A (IR)

The reverse power relay RLZ ( one-phase ) protects the generator from reverse power from the mains. The effective power is detected via a high-precision four- quadrant multiplier which evaluates the effective power regardless of the curve form of the mains voltage. When the reverse power set is exceeded and the timing circuit is completed, the output relay switches through. The switching states are displayed via LED.




Independent Overcurrent / Short-circuit Time Relay IOS310, IOS31G, IOS350, IOS35G
 
IOS 3XY

3-phase AC current monitoring
The highest current value in each phase leads to swich off
Independent power supply with at least 1 phase
Triggers in one-phase operation too
Overcurrent 0.7 - 1.3 (IR) with time release 1 - 30 sec
Short-circuit time release 0.1 - 3 sec
LED displays for exceeding and triggering


Download data sheets (.PDF)
IOS31G 1A (IR), 1,5 - 2,7A (IS)
IOS310 1A (IR), 2,0 - 10A (IS)
IOS35G 5A (IR), 7,5 - 13,5A (IS)
IOS350 5A (IR), 10 - 50A (IS)

3-phase protective device for time-selective overcurrent and short-circuit switch-off in generator and switchgear systems.The unit has an independent power supply and contains 2 seperate trigger circuits with adjustable trigger currents and trigger times. All 3 phases are evaluated individually and the highest value in each phase causes triggering after the value set is exceeded. In the outputs, the switching information is passed on via high-precision two-way contacts ( 250V, 5A ).




Independent Short-circuit Time Relay I-S310, I-S31G, I-S350, I-S35G, I-S354
 
I-S350

3-phase AC current monitoring
The highest current value in each phase leads to switch-off
Independent power supply with at least 1 phase
Triggers in one-phase operation too
Short-circuit time release 0.1 - 3 sec
LED displays for exceeding and triggering


Download data sheets (.PDF)
I-S310 1A (IS), 2,0 - 10A
I-S31G 5A (IS), 10 - 50A

3-phase protective device for time-selective short-circuit switch-off in generator and switchgear systems. The unit has an independent power supply and contains 1 trigger circuit with adjustable trigger currents and trigger times. All 3 phases are evaluated individually and the highest value in each phase causes triggering after the value set is exceeded. In the outputs, the switching information is passed on via high-pecision two-way contacts ( 250V, 5A ).